Vulnerability Note VU#343971ABB PCU400 vulnerable to buffer overflowOverviewABB PCU400 contains a vulnerability which can allow a remote, unauthenticated attacker to execute arbitrary code on a vulnerable system.I. DescriptionThe ABB PCU400 application serves as a communication gateway between RTUs that use the IEC-870-5-104 protocol and the SCADA server. The diagnostic web application contains a software flaw which allows an attacker to gain full access on the PCU400 server by sending a specially crafted packet to the X87 web interface on TCP port 8087.Note that this issue affects PCU400 installations running the IEC60870-5-101/104 protocol based on X87.
According to ABB:
This diagnostic web application is designed to be used locally. Restrictions should be put in place to limit remote access. According to ABB:
Systems Affected
References
This issue was reported by Eyal Udassin and Idan Ofrat of C4 Security. This document was written by Chris Taschner.
If you have feedback, comments, or additional information about this vulnerability, please send us
email. |
|||||||||||||||||||||||||||||
![]() |
|||||||||||||||||||||||||||||||